Case: T10FR01915

Parcel: 11712121C


Addresses:

97 E CONGRESS ST


Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T10FR01915

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
09/10/2010 VIOL - FIRE PROTECTION SYSTEMS Correction Required 906.6 Unobstructed and unobscured.
Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers.

______ Keep all portable fire extinguishers clear from obstructions according to code

904.11.2 System interconnection.
The actuation of the fire extinguishing system shall automatically shut down the fuel or electrical power supply to the cooking equipment. The fuel and electrical supply reset shall be manual.

_____ Have your hood extinguishing system installed with a Micro-switch to automatically cease all electrical power being supplied to your cooking equipment.