Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/11/2010 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.APPROVED. |
| 09/10/2010 |
INSP - FULL |
|
Violation |
1.) TFC 901.4.1 ADDITIONAL SPRINKLER HEADS ARE REQUIRED UNDER DUCT WORK IN OUPATIENT SHELL. |
| 09/10/2010 |
INSP - FULL |
|
Violation |
2.) TFC 901.4.1 1 ADDITIONAL SPRINKLER HEAD IS REQUIRED BENEATH DUCT WORK IN E.R. EQUIPMENT ROOM WEST. |
| 09/10/2010 |
INSP - FULL |
|
Violation |
3.) TFC 901.4.1 IN NORTHWEST CORNER OF E.R. EQUIPMENT ROOM A UPRIGHT HEAD IS MOUNTED IN THE PENDANT POSITION. |
| 09/10/2010 |
INSP - FULL |
|
Violation |
4.) TFC 605.6 IN NORTH SKYWAY ABOVE KITCHEN AN ELECTRICAL JUNCTION BOX NEEDS A COVER PLATE INSTALLED. |
| 09/10/2010 |
INSP - FULL |
|
Violation |
5.) TFC 605.6 INSTALL A COVER PLATE ON ELECTRICAL JUNCTION BOX IN EQUIPMENT ROOM ABOVE ADMINISTRATION. |
| 09/10/2010 |
INSP - FULL |
|
Violation |
6.) TFC 605.7 PROTECTIVE COVER SHIELDS ARE MISSING FROM FUME HOOD MOTORS IN SURGERY EQUIPMENT ROOM SOUTH. |
| 09/10/2010 |
INSP - FULL |
|
Violation |
7.) TFC 605.1 POWER CORD IS MISSING AN APPROVED PLUG IN EDUCTION EQUIPMENT ROOM SOUTH EAST SIDE. CORD IS DUCT TAPED TO OUTLET. |
| 09/10/2010 |
INSP - FULL |
|
Violation |
8.) TFC 703.1.1 SEAL AROUND CABLES IN CONDUIT IN EDUCATION EQUIPMENT ROOM SOUTHEAST SIDE. |
| 09/10/2010 |
INSP - FULL |
|
Violation |
9.) TFC 703.1.1 SEAL AROUND CABLES IN CONDUIT IN 580'S EQUIPMENT ROOM |