Case: T10FR01914

Parcel: 110120960


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T10FR01914

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
10/11/2010 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.APPROVED.
09/10/2010 INSP - FULL Violation 1.) TFC 901.4.1 ADDITIONAL SPRINKLER HEADS ARE REQUIRED UNDER DUCT WORK IN OUPATIENT SHELL.
09/10/2010 INSP - FULL Violation 2.) TFC 901.4.1 1 ADDITIONAL SPRINKLER HEAD IS REQUIRED BENEATH DUCT WORK IN E.R. EQUIPMENT ROOM WEST.
09/10/2010 INSP - FULL Violation 3.) TFC 901.4.1 IN NORTHWEST CORNER OF E.R. EQUIPMENT ROOM A UPRIGHT HEAD IS MOUNTED IN THE PENDANT POSITION.
09/10/2010 INSP - FULL Violation 4.) TFC 605.6 IN NORTH SKYWAY ABOVE KITCHEN AN ELECTRICAL JUNCTION BOX NEEDS A COVER PLATE INSTALLED.
09/10/2010 INSP - FULL Violation 5.) TFC 605.6 INSTALL A COVER PLATE ON ELECTRICAL JUNCTION BOX IN EQUIPMENT ROOM ABOVE ADMINISTRATION.
09/10/2010 INSP - FULL Violation 6.) TFC 605.7 PROTECTIVE COVER SHIELDS ARE MISSING FROM FUME HOOD MOTORS IN SURGERY EQUIPMENT ROOM SOUTH.
09/10/2010 INSP - FULL Violation 7.) TFC 605.1 POWER CORD IS MISSING AN APPROVED PLUG IN EDUCTION EQUIPMENT ROOM SOUTH EAST SIDE. CORD IS DUCT TAPED TO OUTLET.
09/10/2010 INSP - FULL Violation 8.) TFC 703.1.1 SEAL AROUND CABLES IN CONDUIT IN EDUCATION EQUIPMENT ROOM SOUTHEAST SIDE.
09/10/2010 INSP - FULL Violation 9.) TFC 703.1.1 SEAL AROUND CABLES IN CONDUIT IN 580'S EQUIPMENT ROOM