Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/11/2010 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.APPROVED. | |
09/10/2010 | INSP - FULL | Violation | 1.) TFC 901.4.1 ADDITIONAL SPRINKLER HEADS ARE REQUIRED UNDER DUCT WORK IN OUPATIENT SHELL. | |
09/10/2010 | INSP - FULL | Violation | 2.) TFC 901.4.1 1 ADDITIONAL SPRINKLER HEAD IS REQUIRED BENEATH DUCT WORK IN E.R. EQUIPMENT ROOM WEST. | |
09/10/2010 | INSP - FULL | Violation | 3.) TFC 901.4.1 IN NORTHWEST CORNER OF E.R. EQUIPMENT ROOM A UPRIGHT HEAD IS MOUNTED IN THE PENDANT POSITION. | |
09/10/2010 | INSP - FULL | Violation | 4.) TFC 605.6 IN NORTH SKYWAY ABOVE KITCHEN AN ELECTRICAL JUNCTION BOX NEEDS A COVER PLATE INSTALLED. | |
09/10/2010 | INSP - FULL | Violation | 5.) TFC 605.6 INSTALL A COVER PLATE ON ELECTRICAL JUNCTION BOX IN EQUIPMENT ROOM ABOVE ADMINISTRATION. | |
09/10/2010 | INSP - FULL | Violation | 6.) TFC 605.7 PROTECTIVE COVER SHIELDS ARE MISSING FROM FUME HOOD MOTORS IN SURGERY EQUIPMENT ROOM SOUTH. | |
09/10/2010 | INSP - FULL | Violation | 7.) TFC 605.1 POWER CORD IS MISSING AN APPROVED PLUG IN EDUCTION EQUIPMENT ROOM SOUTH EAST SIDE. CORD IS DUCT TAPED TO OUTLET. | |
09/10/2010 | INSP - FULL | Violation | 8.) TFC 703.1.1 SEAL AROUND CABLES IN CONDUIT IN EDUCATION EQUIPMENT ROOM SOUTHEAST SIDE. | |
09/10/2010 | INSP - FULL | Violation | 9.) TFC 703.1.1 SEAL AROUND CABLES IN CONDUIT IN 580'S EQUIPMENT ROOM |