Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2010 | VIOL - MEANS OF EGRESS | Approved | All approved - good job! closed | |
| 09/10/2010 | VIOL - MEANS OF EGRESS | Violation | Blocked exits: 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _______Clear exit area, and maintain it this way. [East and North doors] |
|
| 09/10/2010 | VIOL - MEANS OF EGRESS | Violation | Double keyed lock on door: 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ______ Remove Keyed dead bolt. [North door] - replace with "thumb turn" type. Note: Sprinklers are dated April, 2010 and look real good. Good job! |