Case: T10FR01907

Parcel: 11451216G

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR01907

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
11/01/2010 VIOL - MEANS OF EGRESS Approved All approved - good job! closed
09/10/2010 VIOL - MEANS OF EGRESS Violation Blocked exits:
1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in
this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel.

_______Clear exit area, and maintain it this way. [East and North doors]
09/10/2010 VIOL - MEANS OF EGRESS Violation Double keyed lock on door:
1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

______ Remove Keyed dead bolt. [North door] - replace with "thumb turn" type.


Note: Sprinklers are dated April, 2010 and look real good. Good job!