Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T10FR01884
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/05/2010 | INSP - FULL | Approved | ||
09/08/2010 | INSP - FULL | Violation | COMPLAINT FROM OPERATIONS. NO KEYS IN KEY BOXES. | |
09/08/2010 | INSP - FULL | Violation | 1) SECURE CONTROL VALVES WITH CHAIN AND LOCK. VALVES ARE MONITORED BUT CHAINS WILL PREVENT TAMPERING. CURRENT DOORS ARE NOT ADEQUATE. I WAS ABLE TO REACH THROUGH DECORATIVE DOOR AND TURN VALVE. 2) PROVIDE A SET OF LABELED KEYS FOR EACH LOCK BOX. MASTER KEY, RISER KEY, KEY FOR INTERIOR CORRIDORS. 3) ADDRESS NEEDS TO BE POSTED ON MAIN SIGN. NUMBERS NEED TO BE 15" AND VISIBLE FROM THE STREET. |