Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T10FR01823
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/05/2010 | VIOL - MEANS OF EGRESS | Approved | All approved - good job!! closed | |
08/25/2010 | VIOL - MEANS OF EGRESS | Violation | Double keyed lock on door: 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ______ Remove Keyed dead bolt. ["A" frame annex] |
|
08/25/2010 | VIOL - MEANS OF EGRESS | Violation | Keyed main entry: TFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: [2.2]. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. ______ Place above-mentioned sign on or near front door in an approved manner. [2 at Sanctuary front doors, 1 at "A" frame front door] |