Case: T10FR01823

Parcel: 13324009A


Addresses:

8051 E BROADWAY BL


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T10FR01823

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
10/05/2010 VIOL - BUILDING SVCS & SYSTEMS Approved
08/25/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Electrical wires extending through ceiling:

TFC2006/ 605.5 Flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors.

______ Please remove wires. [Brummet Hall - spot lights- wires thru drywall]
08/25/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Broken outlet:
TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.

______ Please replace outlet in "A" frame kitchen.
08/25/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Open space in electrical panel:

TFC2006 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.

_____Place an approved "blank" in the space.
08/25/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Electrical Room marking:
605.3.1 Labeling. Doors into electrical control panel rooms
shall be marked with a plainly visible and legible sign stating
ELECTRICAL ROOM or similar approved wording.
The disconnecting means for each service, feeder or branch
circuit originating on a switchboard or panelboard shall be
legibly and durably marked to indicate its purpose unless
such purpose is clearly evident.

______ Place a sign on door of electrical panels "Fire- Elect Room" or something of this nature.

______ Place a sign on the Riser room - "Fire Sprinkler Riser" or Riser Room"

______ Place a sign on the "Roof Access" closet door.
08/25/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Tape on breakers:

TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.

__OK_____ Remove tape from breakers.
08/25/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Multiplug adapters:

TFC2006/ 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.

___OK ___Remove noncomplying devices.