Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2010 | VIOL - FIRE PROTECTION SYSTEMS | Approved | NOTE: There were drop bars on the rear door. They have been removed and the cradle for the bar has been ground off / removed - Good job! Closed | |
| 08/24/2010 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Extinguishers / Sprinkler : tagged / inspected: TFC2006/ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ______ Extinguishers shall be maintained, inspected and tagged [annually] in accordance with this code. ______ Provide a sprinkler report with NO deficiencies to Fire Marshal. [Keep on premises for 3 years] |
|
| 08/24/2010 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Extinguishers not mounted: TFC2006/ 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm). ______ Mount extinguishers in an approved manner. |