Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - PRECAUTION AGAINST FIRE
Case Number - T10FR01816
Inspection Description - VIOL - PRECAUTION AGAINST FIRE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/08/2010 | VIOL - PRECAUTION AGAINST FIRE | Approved | ||
08/24/2010 | VIOL - PRECAUTION AGAINST FIRE | Violation | Clearance below sprinklers: TFC 315.2.1 Ceiling clearance. Storage shall be maintained 24 inches (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. ______Remove storage to 18 inches or more below sprinkler head. |
|
08/24/2010 | VIOL - PRECAUTION AGAINST FIRE | Violation | Housekeeping: TFC 304.1 Waste accumulation prohibited. Combustible waste material creating a fire hazard shall not be allowed to accumulate in buildings or structures or upon premises. _______ Clean up oil around and on tanks. Make sure there are no leaks. Provide proof os inspection, testing and approval. Keep area free from oil [downstairs]. Thank you. |