Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/10/2010 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED. |
| 08/24/2010 |
INSP - FULL |
|
Violation |
1.) TFC 703.1.1 SEAL AROUND COMMUNICATION CABLES IN CONDUIT IN 1ST FLOOR I.T. ROOM. |
| 08/24/2010 |
INSP - FULL |
|
Violation |
2.) TFC 1028.2 REMOVE STORAGE BLOCKING EXIT IN TELEPHONE SWITCH ROOM. |
| 08/24/2010 |
INSP - FULL |
|
Violation |
3.) TFC 605.3 REMOVE STORAGE IN FRONT OF ELECTRICAL PANELS IN SUITE #100 ELECTRICAL ROOM. |
| 08/24/2010 |
INSP - FULL |
|
Violation |
4.) TFC 605.4.2 POWER STRIPS IN MARI SURGERY SCHEDULING OFFICE MUST BE INDIVIDUALLY PLUGGED INTO AN OUTLET. |
| 08/24/2010 |
INSP - FULL |
|
Violation |
5.) TFC 605.4.2 POWER STRIPS IN JELENE'S OFFICE IN RESEARCH ON 2ND FLOOR MUST BE INDIVIDUALLY PLUGGED INTO AN OUTLET. |
| 08/24/2010 |
INSP - FULL |
|
Violation |
6.) TFC 901.6 REPLACE MISSING CEILING TILE IN HALLWAY OF SUITE #260. |
| 08/24/2010 |
INSP - FULL |
|
Violation |
7.) TFC 605.4 REMOVE CUBE TYPE MULTI-PLUG ADAPTER IN SUITE #260 CASTING. |
| 08/24/2010 |
INSP - FULL |
|
Violation |
8.) TFC 605.5 EXTENSION CORDS CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING IN 2ND FLOOR CONFERENCE ROOM. |
| 08/24/2010 |
INSP - FULL |
|
Violation |
9.) TFC 605.6 INSTALL A COVER PLATE ON OUTLET IN SUITE #230 CODING OFFICE. |
| 08/24/2010 |
INSP - FULL |
|
Violation |
10.) TFC 605.6 INSTALLL A COVER PLATE ON ELECTRICAL JUNCTION BOX IN TRANSCRIPTION CUBICLE. |
| 08/24/2010 |
INSP - FULL |
|
Violation |
11.) TFC 605.5 THE EXTENSION CORD BEING USED IN TRANSCRIPTION CUBICLE CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING. |
| 08/24/2010 |
INSP - FULL |
|
Violation |
12.) TFC 605.4.2 POWER STRIPS IN DR. P'S DICTATION AREA CANNOT BE CONNECTED IN SERIES. |
| 08/24/2010 |
INSP - FULL |
|
Violation |
13.) TFC 315.2.1 LOWER STORAGE IN DR. LEVI'S STORAGE CLOSET TO 18" BELOW SPRINKLER HEAD DEFLECTOR. |
| 08/24/2010 |
INSP - FULL |
|
Violation |
14.) TFC 605.4.2 POWER STRIPS CANNOT BE CONNECTED IN SERIES IN DIANA SERAFIN'S CUBICLE IN SUITE #260. |