Case: T10FR01804

Parcel: 110120950


Addresses:

2424 N WYATT DR


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T10FR01804

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
09/10/2010 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED.
08/24/2010 INSP - FULL Violation 1.) TFC 703.1.1 SEAL AROUND COMMUNICATION CABLES IN CONDUIT IN 1ST FLOOR I.T. ROOM.
08/24/2010 INSP - FULL Violation 2.) TFC 1028.2 REMOVE STORAGE BLOCKING EXIT IN TELEPHONE SWITCH ROOM.
08/24/2010 INSP - FULL Violation 3.) TFC 605.3 REMOVE STORAGE IN FRONT OF ELECTRICAL PANELS IN SUITE #100 ELECTRICAL ROOM.
08/24/2010 INSP - FULL Violation 4.) TFC 605.4.2 POWER STRIPS IN MARI SURGERY SCHEDULING OFFICE MUST BE INDIVIDUALLY PLUGGED INTO AN OUTLET.
08/24/2010 INSP - FULL Violation 5.) TFC 605.4.2 POWER STRIPS IN JELENE'S OFFICE IN RESEARCH ON 2ND FLOOR MUST BE INDIVIDUALLY PLUGGED INTO AN OUTLET.
08/24/2010 INSP - FULL Violation 6.) TFC 901.6 REPLACE MISSING CEILING TILE IN HALLWAY OF SUITE #260.
08/24/2010 INSP - FULL Violation 7.) TFC 605.4 REMOVE CUBE TYPE MULTI-PLUG ADAPTER IN SUITE #260 CASTING.
08/24/2010 INSP - FULL Violation 8.) TFC 605.5 EXTENSION CORDS CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING IN 2ND FLOOR CONFERENCE ROOM.
08/24/2010 INSP - FULL Violation 9.) TFC 605.6 INSTALL A COVER PLATE ON OUTLET IN SUITE #230 CODING OFFICE.
08/24/2010 INSP - FULL Violation 10.) TFC 605.6 INSTALLL A COVER PLATE ON ELECTRICAL JUNCTION BOX IN TRANSCRIPTION CUBICLE.
08/24/2010 INSP - FULL Violation 11.) TFC 605.5 THE EXTENSION CORD BEING USED IN TRANSCRIPTION CUBICLE CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING.
08/24/2010 INSP - FULL Violation 12.) TFC 605.4.2 POWER STRIPS IN DR. P'S DICTATION AREA CANNOT BE CONNECTED IN SERIES.
08/24/2010 INSP - FULL Violation 13.) TFC 315.2.1 LOWER STORAGE IN DR. LEVI'S STORAGE CLOSET TO 18" BELOW SPRINKLER HEAD DEFLECTOR.
08/24/2010 INSP - FULL Violation 14.) TFC 605.4.2 POWER STRIPS CANNOT BE CONNECTED IN SERIES IN DIANA SERAFIN'S CUBICLE IN SUITE #260.