Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T10FR01804
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2010 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED. | |
| 08/24/2010 | INSP - FULL | Violation | 1.) TFC 703.1.1 SEAL AROUND COMMUNICATION CABLES IN CONDUIT IN 1ST FLOOR I.T. ROOM. | |
| 08/24/2010 | INSP - FULL | Violation | 2.) TFC 1028.2 REMOVE STORAGE BLOCKING EXIT IN TELEPHONE SWITCH ROOM. | |
| 08/24/2010 | INSP - FULL | Violation | 3.) TFC 605.3 REMOVE STORAGE IN FRONT OF ELECTRICAL PANELS IN SUITE #100 ELECTRICAL ROOM. | |
| 08/24/2010 | INSP - FULL | Violation | 4.) TFC 605.4.2 POWER STRIPS IN MARI SURGERY SCHEDULING OFFICE MUST BE INDIVIDUALLY PLUGGED INTO AN OUTLET. | |
| 08/24/2010 | INSP - FULL | Violation | 5.) TFC 605.4.2 POWER STRIPS IN JELENE'S OFFICE IN RESEARCH ON 2ND FLOOR MUST BE INDIVIDUALLY PLUGGED INTO AN OUTLET. | |
| 08/24/2010 | INSP - FULL | Violation | 6.) TFC 901.6 REPLACE MISSING CEILING TILE IN HALLWAY OF SUITE #260. | |
| 08/24/2010 | INSP - FULL | Violation | 7.) TFC 605.4 REMOVE CUBE TYPE MULTI-PLUG ADAPTER IN SUITE #260 CASTING. | |
| 08/24/2010 | INSP - FULL | Violation | 8.) TFC 605.5 EXTENSION CORDS CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING IN 2ND FLOOR CONFERENCE ROOM. | |
| 08/24/2010 | INSP - FULL | Violation | 9.) TFC 605.6 INSTALL A COVER PLATE ON OUTLET IN SUITE #230 CODING OFFICE. | |
| 08/24/2010 | INSP - FULL | Violation | 10.) TFC 605.6 INSTALLL A COVER PLATE ON ELECTRICAL JUNCTION BOX IN TRANSCRIPTION CUBICLE. | |
| 08/24/2010 | INSP - FULL | Violation | 11.) TFC 605.5 THE EXTENSION CORD BEING USED IN TRANSCRIPTION CUBICLE CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING. | |
| 08/24/2010 | INSP - FULL | Violation | 12.) TFC 605.4.2 POWER STRIPS IN DR. P'S DICTATION AREA CANNOT BE CONNECTED IN SERIES. | |
| 08/24/2010 | INSP - FULL | Violation | 13.) TFC 315.2.1 LOWER STORAGE IN DR. LEVI'S STORAGE CLOSET TO 18" BELOW SPRINKLER HEAD DEFLECTOR. | |
| 08/24/2010 | INSP - FULL | Violation | 14.) TFC 605.4.2 POWER STRIPS CANNOT BE CONNECTED IN SERIES IN DIANA SERAFIN'S CUBICLE IN SUITE #260. |