Case: T10FR01783

Parcel: 125111530


Addresses:

3809 E 3RD ST


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T10FR01783

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
09/08/2010 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED.
08/20/2010 INSP - FULL Violation 1.) TFC 605.4.2 THE POWER STRIPS IN ROOM F MUST BE INDIVIDUALLY PLUGGED INTO AN OUTLET.
08/20/2010 INSP - FULL Violation 2.) TFC 605.5 EXTENSION CORD POWERING REFIDGERATOR IN STORAGE ROOM BETWEEN ROOM E AND F IS NOT APPROVED FOR PERMANENT USE.
08/20/2010 INSP - FULL Violation 3.) TFC 605.1 OPEN SLOTS IN ELECTRICAL PANEL IN REFRIDGERATOR ROOM MUST HAVE BLANKS INSTALLED TO COVER EXPOSURE TO WIRING.
08/20/2010 INSP - FULL Violation 4.) TFC 1008.1.8.4 REMOVE SLIDE LOCK FROM EXTERIOR OF FRONT EXIT GATE FROM THE PLAYGROUND.
08/20/2010 INSP - FULL Violation 5.) TFC 901.6.2 THE FIRE ALARM SYSTEM ANNUAL INSPECTION REPORT MUST BE SUBMITTED UPON RE-INSPECTION.