Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T10FR01748
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/17/2010 | VIOL - MEANS OF EGRESS | Correction Required | IFC 1027.3 Exit sign illumination. Exit signs shall be internally externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1. The EXIT sign located by the shoes area shall be illuminated. _____2. The EXIT sign located above the north exit door shall be illuminated. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |