Case: T10FR01742

Parcel: 13321074A


Addresses:

6367 E BROADWAY BL


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T10FR01742

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
09/17/2010 VIOL - FIRE PROTECTION SYSTEMS Approved
08/17/2010 VIOL - FIRE PROTECTION SYSTEMS Violation Extinguishing system service:
904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion.

______ Hood system to be serviced, tested and tagged every 6 months. [Keep clean - including the "pull station"]

904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall
state the extent, time and date of cleaning. Such records shall be maintained on the premises.
08/17/2010 VIOL - FIRE PROTECTION SYSTEMS Violation TFC2006/ 906.5 Conspicuous Location

TFC 906.6 Unobstructed and unobscured. Fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers.

______ Mount a ABC extinguisher in an approved manner.