Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T10FR01725
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/29/2010 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPORVED. | |
| 08/16/2010 | INSP - FULL | Violation | 1.) TFC 1011.1 AN APPROVED EXIT SIGN WITH A DIRECTIONAL ARROW IS REQUIRED IN HALLWAY BY SUITE #131. | |
| 08/16/2010 | INSP - FULL | Violation | 2.) TFC 906.1 REPAIR CEILING PENETRATIONS IN TELEPHONE CLOSET. | |
| 08/16/2010 | INSP - FULL | Violation | 3.) TFC 1008.1.8 THE NORTH SIDE EXIT DOORS ON THE FIRST FLOOR MUST HAVE THUMB TURN LATCHES ON THE DEAD BOLT LOCKS. DOUBLE KEYED DEAD BOLTS ARE NOT PERMITTED BY THE FIRE CODE. | |
| 08/16/2010 | INSP - FULL | Violation | 4.) TFC 906.1 REPAIR WALL PENETRATION IN FIRST FLOOR JANITOR'S CLOSET. | |
| 08/16/2010 | INSP - FULL | Violation | 5.) TFC 605.6 INSTALL A COVER PLATE ON ELECTRICAL OUTLET IN ROOM # 226. | |
| 08/16/2010 | INSP - FULL | Violation | 6.) TFC 1006.3 REPAIR THE EMERGENCY ILLUMINATION UNITS ON THE 2ND FLOOR TO OPERATE PROPERLY. | |
| 08/16/2010 | INSP - FULL | Violation | 7.) TFC 901.6.2 A CURRENT ANNUAL INSPECTION REPORT FOR THE SPRINKLER SYSTEM MUST BE SUBMITTED. ALSO THE 5 YEAR INTERNAL INSPECTION OF THE RISER CHECK VALVE IS PAST DUE. | |
| 08/16/2010 | INSP - FULL | Violation | 8.) TFC 901.6.2 A CURRENT FIRE ALARM SYSTEM INSPECTION REPORT MUST BE SUBMITTED UPON RE-INSPECTION. |