Case: T10FR01725

Parcel: 127035510


Addresses:

630 N CRAYCROFT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T10FR01725

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
10/29/2010 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPORVED.
08/16/2010 INSP - FULL Violation 1.) TFC 1011.1 AN APPROVED EXIT SIGN WITH A DIRECTIONAL ARROW IS REQUIRED IN HALLWAY BY SUITE #131.
08/16/2010 INSP - FULL Violation 2.) TFC 906.1 REPAIR CEILING PENETRATIONS IN TELEPHONE CLOSET.
08/16/2010 INSP - FULL Violation 3.) TFC 1008.1.8 THE NORTH SIDE EXIT DOORS ON THE FIRST FLOOR MUST HAVE THUMB TURN LATCHES ON THE DEAD BOLT LOCKS. DOUBLE KEYED DEAD BOLTS ARE NOT PERMITTED BY THE FIRE CODE.
08/16/2010 INSP - FULL Violation 4.) TFC 906.1 REPAIR WALL PENETRATION IN FIRST FLOOR JANITOR'S CLOSET.
08/16/2010 INSP - FULL Violation 5.) TFC 605.6 INSTALL A COVER PLATE ON ELECTRICAL OUTLET IN ROOM # 226.
08/16/2010 INSP - FULL Violation 6.) TFC 1006.3 REPAIR THE EMERGENCY ILLUMINATION UNITS ON THE 2ND FLOOR TO OPERATE PROPERLY.
08/16/2010 INSP - FULL Violation 7.) TFC 901.6.2 A CURRENT ANNUAL INSPECTION REPORT FOR THE SPRINKLER SYSTEM MUST BE SUBMITTED. ALSO THE 5 YEAR INTERNAL INSPECTION OF THE RISER CHECK VALVE IS PAST DUE.
08/16/2010 INSP - FULL Violation 8.) TFC 901.6.2 A CURRENT FIRE ALARM SYSTEM INSPECTION REPORT MUST BE SUBMITTED UPON RE-INSPECTION.