Case: T10FR01700

Parcel: 10609062C

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
08/12/2010 VIOL - MEANS OF EGRESS Correction Required IFC 1027.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated. The face of an exit sign illuminated
from an external source, shall have an intensity of not less than
5 foot-candles (54 lux). Internally illuminated signs shall provide
equivalent luminance and be listed for the purpose.

_____1. Repair or replace the EXIT sign located above the east exit doors.

_____2. Repair or replace the EXIT sign located near the west exit door.
08/12/2010 VIOL - MEANS OF EGRESS Correction Required IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system.

_____1. Repair or replace the emergency lighting unit located on the south wall.