Case: T10FR01700

Parcel: 10609062C

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
08/12/2010 VIOL - BUILDING SVCS & SYSTEMS Correction Required IFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.

_____1. Remove the cube adapter located in the stock room by the restroom.
NOTE: Replace the cube adapter with a fused power-strip.
08/12/2010 VIOL - BUILDING SVCS & SYSTEMS Correction Required IFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used.

_____1. The electrical wiring located in the stock room shall be protected by conduit. All wiring and electrical repair shall be done by a licensed electrician.