Case: T10FR01694

Parcel: 13414018D


Addresses:

1011 S PRUDENCE RD

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
10/14/2010 INSP - FULL Approved
08/11/2010 INSP - FULL Correction Required 1. _____ 315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms.

2. 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
- A. SPRINKLER SYSTEM SAHLL BE SERVICED ANNUALLY
- B. SPRINKLER SYSTEM SHALL BE EXTENDED TO MAINTAIN COVERAGE:
- SHOP MANAFER'S OFFICE
- AN AWNING HAS BEEN BUILT THAT HAS HAMPERED THE SPRINKLER COVERAGE. HEAD SHALL BE ADDED UNDER THE COVERING.

3. _____ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, back-up power shall be supplied
- Provide back up power supply for all required exit illumination
- OUTSIDE THE SHOP MANAGER'S OFFICE
- BAY #1 EXIT

4. _____ 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
- ROOF OF SHOP MANAGER'S OFFICE
- WEST WALL OF SHOP MANAGER

5. __X___ 3003.5 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel in accordance with Sections 3003.3.1 through 3003.3.3.
- BAY #3 (CORRECTED IN MY PRESENCE)

6. _____ 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied
- FIRE EXTINGUISHER SHALL BE SERVICED ANNUALLY AND PROPERLY MOUNTED IN BAY #3