Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T10FR01677

Parcel: 140122200


Addresses:

2048 E IRVINGTON RD


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR01677

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
09/01/2010 VIOL - MEANS OF EGRESS Approved ALL VIOLATIONS ABATED.
08/10/2010 VIOL - MEANS OF EGRESS Correction Required 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system

1___ REPAIR EMERGENCY LIGHT AT NORTH EAST CORNER OF POLL ROOM.
2___ EMERGENCY LIGHT NOT WORKING AT SOUTH END OF BAR
08/10/2010 VIOL - MEANS OF EGRESS Correction Required 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed.

1___ NEED TO REPAIR ALL EXIT SIGNS. BACKUP BATTERIES ARE OUT.