Case: T10FR01643

Parcel: 12618135A


Addresses:

4101 E 22ND ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
08/23/2010 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPORVED.
08/09/2010 INSP - FULL Violation 1.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN FRONT OFFICE.
08/09/2010 INSP - FULL Violation 2.) TFC 605.4.2 POWER STRIPS ARE PIGGY BACKED IN EMPLOYEE RESOURCE OFFICE.
08/09/2010 INSP - FULL Violation 3.) TFC 605.4 THE CUBE TYPE MULTI-PLUG ADAPTER IN INFANT ROOM IS NOT PERMITTED BY THE FIRE CODE.
08/09/2010 INSP - FULL Violation 4.) TFC 1006.3 THE EMERGENCY ILLUMINTATION UNIT AT WEST END OF HALLWAY IS NOT OPERATING.
08/09/2010 INSP - FULL Violation 5.) TFC 901.6.2 THE FIRE ALARM SYSTEM ANNUAL INSPECTION REPORT MUST BE SUBMITTED UPON RE-INSPECTION.