Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T10FR01590
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/03/2010 | VIOL - MEANS OF EGRESS | Violation | 1003.6 - Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear exit path, and maintain it this way. |
|
08/03/2010 | VIOL - MEANS OF EGRESS | Violation | 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. _____ Repair or replace emergency lighting |
|
08/03/2010 | VIOL - MEANS OF EGRESS | Violation | 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists:2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. |