Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T10FR01551
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/10/2010 | INSP - FULL | Approved | ALL NOTED TFC VIOLATION HAVE BEEN CORRECTED. APPROVED. | |
07/30/2010 | INSP - FULL | Violation | 1.) TFC 901.6 REPAIR CEILING PENETRATION IN WEST E/S CLOSET OF PACU. | |
07/30/2010 | INSP - FULL | Violation | 2.) TFC 1011.4 EXIT SIGN IS NOT ILLUMINATED IN STAIRWELL NORTH OF O.R. MANAGER'S OFFICE. | |
07/30/2010 | INSP - FULL | Violation | 3.) TFC 703.1.1 REPAIR WALL PENETRATIONS IN PRE-OP I/S ROOM NEXT TO ELEVATOR. | |
07/30/2010 | INSP - FULL | Violation | 4.) TFC 901.6 REPLACE MISSING CEILING TILE ON 2ND FLOOR M.O.R. CLASSROOM. | |
07/30/2010 | INSP - FULL | Violation | 5.) TFC 703.1.1 SEAL PENETRATIONS IN CEILING AND SEAL AROUND CABLES IN CINDUIT IN I/S ROOM BEHIND M.O.R. CLASSROOM. | |
07/30/2010 | INSP - FULL | Violation | 6.) TFC 1011.4 AN APPROVED EXIT SIGN IS REQUIRED AT SOUTH EXIT OUTSIDE OF VENDOR ROOM ON 2ND FLOOR. | |
07/30/2010 | INSP - FULL | Violation | 7.) TFC 1020.1.1 IN SOUTH O.R. CORRIDOR BY NURSES'S STATION THE ELECTRO-MAGNETIC HOLD-OPEN DEVICES FOR FIRE RATED DOORS ARE NOT OPERATING. DOORS ARE BEING MECHANICALLY PROPPED OPEN. | |
07/30/2010 | INSP - FULL | Violation | 8.) TFC 703.1.1 SEAL WALL PENETRATION BEHIND DOOR IN O.R. SOUTH CORRIDOR EAST EXIT IN FORYER. | |
07/30/2010 | INSP - FULL | Violation | 9.) TFC 901.6 REPLACE MISSING CEILING TILE IN O.R. SOUTH CORRIDOR WEST EXIT I/S ROOM. | |
07/30/2010 | INSP - FULL | Violation | 10.) TFC 901.6 RE-SECURE LIGHT TO CEILING IN AMBULATORY SURGERY CENTER AUTO CLAVE ROOM BETWEEN SUITES 1 & 2. |