Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T10FR01511

Parcel: 132191160


Addresses:

2175 E IRVINGTON RD


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T10FR01511

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
08/23/2010 VIOL - FIRE PROTECTION SYSTEMS Approved ALL VIOLATIONS ABATED.
07/28/2010 VIOL - FIRE PROTECTION SYSTEMS Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

1___ SHOW SPRINKLER SYSTEM HAS BEEN INSPECT AND TESTED WITHIN THE YEAR. CORRECT DEFICIENCIES.