Case: T10FR01449

Parcel: 136087620


Addresses:

9520 E 22ND ST


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T10FR01449

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
08/05/2010 INSP - FULL Approved All discrepencies completed
07/22/2010 INSP - FULL Correction Required 906.6 Unobstructed and unobscured. Portable fire
extinguishers shall not be obstructed or obscured from view. In
rooms or areas in which visual obstruction cannot be completely
avoided, means shall be provided to indicate the locations
of extinguishers.
-Unblock the extinguisher
07/22/2010 INSP - FULL Correction Required 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.
07/22/2010 INSP - FULL Correction Required 605.5 Extension cords. Extension cords and flexible cords
shall not be a substitute for permanent wiring.

-Remove extension cord by the register