Case: T10FR01445

Parcel: 13008380B


Addresses:

1550 S ALVERNON WY

Inspection Status: Correction Required

Inspection History: VIOL - FLAMMABLE LIQUIDS

Date Description Inspector Results Comments
07/22/2010 VIOL - FLAMMABLE LIQUIDS Correction Required 3404.2.13.1.1 Temporarily out of service. Underground tanks temporarily out of service shall have the fill line, gauge opening, vapor return and pump connection secure against tampering. Vent lines shall remain open and be maintained in accordance with Sections 3404.2.7.3 and 3404.2.7.4.

3404.2.13.1.2 Out of service for 90 days. Underground tanks not used for a period of 90 days shall be safeguarded in accordance with all the following or be removed in accordance with Section 3404.2.14:
1. Flammable or combustible liquids shall be removed from the tank.
2. All piping, including fill line, gauge opening, vapor return and pump connection, shall be capped or plugged and secured from tampering.
3. Vent lines shall remain open and be maintained in accordance with Sections 3404.2.7.3 and 3404.2.7.4.

3404.2.13.1.3 Out of service for one year. Underground tanks that have been out of service for a period of one year shall be removed from the ground in accordance with Section 3404.2.14 or abandoned in place in accordance with Section 3404.2.13.1.4
07/22/2010 VIOL - FLAMMABLE LIQUIDS Continued Met with the owner, the station has been secured and place out of service as of 07-22-2010.