Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/10/2010 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED. |
| 07/19/2010 |
INSP - FULL |
|
Violation |
1.) TFC 605.4.2 PIGGY BACKED POWER STRIPS IN NUMEROUS CUBICLES OF TECH. MANAGEMENT MUST BE PLUGGED DIRECTLY INTO AN OUTET. |
| 07/19/2010 |
INSP - FULL |
|
Violation |
2.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON ON NORTH SIDE OF TECH MANAGEMENT. |
| 07/19/2010 |
INSP - FULL |
|
Violation |
3.) TFC 605.5 EXTENSION CORDS CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING IN 3RD CUBICLE ON NORTH WALL OF TECH MAGAGEMENT . |
| 07/19/2010 |
INSP - FULL |
|
Violation |
4.) TFC 703.1.1 REPAIR NUMEROUS CEILING PENETRATIONS THROUGHOUT TECH. MANAGEMENT. |
| 07/19/2010 |
INSP - FULL |
|
Violation |
5.) TFC 901.6 REPLACE MISSING CEILING TILE IN STORAGE AREA OF TECH MANAGEMENT. |
| 07/19/2010 |
INSP - FULL |
|
Violation |
6.) TFC 315.2.1 MAINTAIN STORAGE AT OR BELOW 18" BELOW THE SPRINKLER HEAD DEFLECTOR IN STORAGE AREA OF TECH MANAGEMENT. |
| 07/19/2010 |
INSP - FULL |
|
Violation |
7.) TFC 901.6 REPALCE MISSING CEILING TILE IN TECH MANAGEMENT MANAGER'S OFFICE. |
| 07/19/2010 |
INSP - FULL |
|
Violation |
8.) TFC 605.4.2 PIGGY BACKED POWER STRIPS IN CENTRAL CUIBICLE OF IN PATIENT PHARMACY MUST EACH BE PLUGGED DIRECTLY INTO AN OUTLET. |
| 07/19/2010 |
INSP - FULL |
|
Violation |
9.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN BREAK ROOM OF IN PATEINT PHARMACY. |
| 07/19/2010 |
INSP - FULL |
|
Violation |
10.) TFC 605.6 INSTALL A COVER PLATE ON OUTLET IN BREAK ROOM OF IN PATIENT PHARMACY. |
| 07/19/2010 |
INSP - FULL |
|
Violation |
11.) TFC 901.6 REPAIR CEILING PENETRATIONS IN SECURITY CAMERA ROOM. |
| 07/19/2010 |
INSP - FULL |
|
Violation |
12.) TFC 901.6 REPAIR CEILING PENETRATIONS IN MAIN TELEPHONE SWITCH ROOM. |
| 07/19/2010 |
INSP - FULL |
|
Violation |
13.) TFC 901.6 REPAIR CEILING PENETRATIONS IN CAMERA ROOM OF IN PATIENT MONITORING. |
| 07/19/2010 |
INSP - FULL |
|
Violation |
14.) TFC 605.6 INSTALL A COVER PLATE ON ELECTRICAL JUNCTION BOX IN CAMERA ROOM OF IN PATIENT MONITORING. |
| 07/19/2010 |
INSP - FULL |
|
Violation |
15.) TFC 901.6 PUT CEILING TILE BACK IN PLACE OUTSIDE OF CHAPEL AT CORRIDOR INTERSECTION. |
| 07/19/2010 |
INSP - FULL |
|
Violation |
16.) TFC 901.6 REPLACE MISSING CEILING TILE IN CORRIDOR OF HELIPORT SOUTH ENTRANCE. |
| 07/19/2010 |
INSP - FULL |
|
Violation |
17.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN CORRIDOR OF HELIPORT SOUTH ENTRANCE. |