Case: T10FR01383

Parcel: 110120960


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T10FR01383

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
09/10/2010 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. APPROVED.
07/19/2010 INSP - FULL Violation 1.) TFC 605.4.2 PIGGY BACKED POWER STRIPS IN NUMEROUS CUBICLES OF TECH. MANAGEMENT MUST BE PLUGGED DIRECTLY INTO AN OUTET.
07/19/2010 INSP - FULL Violation 2.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON ON NORTH SIDE OF TECH MANAGEMENT.
07/19/2010 INSP - FULL Violation 3.) TFC 605.5 EXTENSION CORDS CANNOT BE A SUBSTITUTE FOR PERMANENT WIRING IN 3RD CUBICLE ON NORTH WALL OF TECH MAGAGEMENT .
07/19/2010 INSP - FULL Violation 4.) TFC 703.1.1 REPAIR NUMEROUS CEILING PENETRATIONS THROUGHOUT TECH. MANAGEMENT.
07/19/2010 INSP - FULL Violation 5.) TFC 901.6 REPLACE MISSING CEILING TILE IN STORAGE AREA OF TECH MANAGEMENT.
07/19/2010 INSP - FULL Violation 6.) TFC 315.2.1 MAINTAIN STORAGE AT OR BELOW 18" BELOW THE SPRINKLER HEAD DEFLECTOR IN STORAGE AREA OF TECH MANAGEMENT.
07/19/2010 INSP - FULL Violation 7.) TFC 901.6 REPALCE MISSING CEILING TILE IN TECH MANAGEMENT MANAGER'S OFFICE.
07/19/2010 INSP - FULL Violation 8.) TFC 605.4.2 PIGGY BACKED POWER STRIPS IN CENTRAL CUIBICLE OF IN PATIENT PHARMACY MUST EACH BE PLUGGED DIRECTLY INTO AN OUTLET.
07/19/2010 INSP - FULL Violation 9.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN BREAK ROOM OF IN PATEINT PHARMACY.
07/19/2010 INSP - FULL Violation 10.) TFC 605.6 INSTALL A COVER PLATE ON OUTLET IN BREAK ROOM OF IN PATIENT PHARMACY.
07/19/2010 INSP - FULL Violation 11.) TFC 901.6 REPAIR CEILING PENETRATIONS IN SECURITY CAMERA ROOM.
07/19/2010 INSP - FULL Violation 12.) TFC 901.6 REPAIR CEILING PENETRATIONS IN MAIN TELEPHONE SWITCH ROOM.
07/19/2010 INSP - FULL Violation 13.) TFC 901.6 REPAIR CEILING PENETRATIONS IN CAMERA ROOM OF IN PATIENT MONITORING.
07/19/2010 INSP - FULL Violation 14.) TFC 605.6 INSTALL A COVER PLATE ON ELECTRICAL JUNCTION BOX IN CAMERA ROOM OF IN PATIENT MONITORING.
07/19/2010 INSP - FULL Violation 15.) TFC 901.6 PUT CEILING TILE BACK IN PLACE OUTSIDE OF CHAPEL AT CORRIDOR INTERSECTION.
07/19/2010 INSP - FULL Violation 16.) TFC 901.6 REPLACE MISSING CEILING TILE IN CORRIDOR OF HELIPORT SOUTH ENTRANCE.
07/19/2010 INSP - FULL Violation 17.) TFC 901.6 REPLACE MISSING SPRINKLER HEAD ESCUTCHEON IN CORRIDOR OF HELIPORT SOUTH ENTRANCE.