Case: T10FR01362

Parcel: 14016003E


Addresses:

5010 S CAMPBELL AV


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR01362

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
08/31/2010 VIOL - MEANS OF EGRESS Approved ALL VIOLATIONS ABATED.
07/15/2010 VIOL - MEANS OF EGRESS Correction Required 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system

1___ REPAIR EMERGENCY LIGHT ON REAR EXIT DOOR.
07/15/2010 VIOL - MEANS OF EGRESS Correction Required 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed.

1___ REPAIR LIGHT OVER NORTH EXIT DOOR.
07/15/2010 VIOL - MEANS OF EGRESS Correction Required 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

1___ REMOVE KEYED LOCK ON REAR KITCHEN EXIT DOOR.