Case: T10FR01342

Parcel: 123020090


Addresses:

2938 E GRANT RD

Inspection Status: Correction Required

Inspection History: INSP - FULL

Date Description Inspector Results Comments
07/15/2010 INSP - FULL Correction Required 96 12.1.2.4 - FRYERS SHALL BE INSTALLED WITH AT LEAST A SIXTEEN INCH SPACE BETWEEN TEH APPLIANCE AND FLAMES OF ANOTHER

96 12.1.2.5 - IF A STEEL OR TEMPERED GLASS BAFFLE IS INSTALLED AT A MINIMUM OF EIGHT INCHES, SIXTEEN INCH SPACING DOES NOT APPLY

Comment: Detectors & Detector Brackets need to be properly cleaned when hood is cleaned. Grease build-up can cause detection system not to function properly