Case: T10FR01339

Parcel: 12206003A


Addresses:

4310 E GRANT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T10FR01339

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
07/19/2010 INSP - FULL Approved
07/14/2010 INSP - FULL Correction Required 96 12.1.2.4 FRYERS SHALL BE INSTALLED WITH AT LEAST A 16 INCH SPACE BETWEEN The APPLIANCES AND FLAME OF ANOTHER

96 12.1.2.5 - IF A STEEL OR TEMPERED GLASS BAFFLE IS INSTALLED AT A MIN OF 8 INCHES, 16 INCH SPACING DOES NOT APPLY

COMMENTS: Metal Baffle (barrier) between the fryer and the range is required to be in compliance with fire code