Case: T10FR01305

Parcel: 12801005H

Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T10FR01305

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
07/07/2010 INSP - FULL Violation TFC 904.11.6.4 - Extinguishing system service.
Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion.

_____ Provide a copy of your most recent hood system report.
system tagged __/__/__ by _____________________

TFC 107.1 - Maintenance of safeguards.
Whenever or wherever any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provisions of this code, or otherwise installed, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with this code and applicable referenced standards.

_____ Emergency egress light - South sink area

_____ Emergency egress light - outside office

_____ Replace front door for deep fryer

TFC - 3003.5.3 - Securing compressed gas containers...
Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity.

_____ Small CO2 tank

TFC 315.2.1 - Ceiling clearance.
Storage shall be maintained… a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of buildings.

_____ Provide and maintain 18" clearance below sprinkler head deflectors (Freezer).