Case: T10FR01302

Parcel: 11205283E


Addresses:

2854 N CAMPBELL AV


Inspection Status: Correction Required

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Case Number - T10FR01302

Inspection Description - VIOL - PRECAUTION AGAINST FIRE

Inspection Status - Correction Required

Date Description Inspector Results Comments
07/12/2010 VIOL - PRECAUTION AGAINST FIRE Correction Required 315.2.1 Ceiling clearance
Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building.

_____ Maintain proper ceiling clearance according to code.
07/12/2010 VIOL - PRECAUTION AGAINST FIRE Correction Required 315.2.3 Equipment rooms
Combustible materials shall not be stored in boiler rooms, mechanical rooms, or electrical equipment rooms.

_____Remove all combustibles from mechanical room.