Case: T10FR01292

Parcel: 120074660


Addresses:

4420 S 6TH AV

Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
07/07/2010 VIOL - MEANS OF EGRESS Violation 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate…
The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator.

_____ Repair or replace emergency lighting
07/07/2010 VIOL - MEANS OF EGRESS Violation 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Exception,…….
To ensure that there is no confusion on the required exiting from the building the following must be completed:
1. A sign stating "NOT AN EXIT" affixed to the interior side of the door. The sign shall consist of letters having a principal stroke of not less than 0.75 inch wide and at least 6 inches high on a contrasting background.
2. A sign stating "THIS DOOR BLOCKED" affixed to the exterior side of the door. The sign shall consist of letters having a principal stroke of not less than 0.75 inch wide and at least 6 inches high on a contrasting background.
07/07/2010 VIOL - MEANS OF EGRESS Violation 1011.2 - Illumination. Exit signs shall be internally or externally illuminated.

_____ Repair/replace exit signs