Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T10FR01282

Parcel: 13734001A


Addresses:

1650 W VALENCIA RD


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T10FR01282

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
06/30/2010 VIOL - BUILDING SVCS & SYSTEMS Violation 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment.
_____ Clear area around electrical panels
06/30/2010 VIOL - BUILDING SVCS & SYSTEMS Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage
or physical impact. Extension cords shall be used only with portable appliances.

__Remove/replace all unprotected extension cords being used as permanent wiring.
06/30/2010 VIOL - BUILDING SVCS & SYSTEMS Violation 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.
__ Photo shop