Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/11/2010 | INSP - FULL | Approved | Ceiling tiles replaced and extension cord removed | |
| 07/27/2010 | INSP - FULL | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. " Replace the tiles in the storage area to prevent the travel of smoke and flame in case of a fire. |
|
| 07/27/2010 | INSP - FULL | Correction Required | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. -Replace the extension cord near the register with a power strip or permenant wire. |