Case: T10FR01270

Parcel: 12618111B


Addresses:

3901 E 22ND ST


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T10FR01270

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
09/21/2010 INSP - FULL Approved
08/16/2010 INSP - FULL Continued Exit sign batteries on order
07/29/2010 INSP - FULL Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated.
Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.

Replace the tiles in the storage area to prevent the travel of smoke and flame in case of a fire.
07/29/2010 INSP - FULL Correction Required 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

" Replace the missing outlet cover near the ice cream tub.
07/29/2010 INSP - FULL Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.

Fire extinguishers shall be inspected annually. You can remove the 1 expired extinguisher. You have more than enough.

- Also remove the extinguisher sign on the wall without a extinguisher.
07/29/2010 INSP - FULL Correction Required 1011.4 Internally illuminated exit signs. Internally illuminated exit signs shall be listed and labeled and shall be installed in accordance with the manufacturer's instructions and Section 2702 of the International Building Code. Exit signs shall be illuminated at all times.

" The exit signs back up power is not working. Please repair or replace the sign to ensure it is lit at all times and has a minimum of a 90 minute back up power source.
07/29/2010 INSP - FULL Continued 3003.5.3 Securing compressed gas containers, cylinders
and tanks. Compressed gas containers, cylinders and tanks
shall be secured to prevent falling caused by contact, vibration
or seismic activity.

-Please keep the CO2 cylinder chained
07/29/2010 INSP - FULL Correction Required 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers on approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property.

Address requirements attached. Please ensure the address faces 22nd street.
07/29/2010 INSP - FULL Correction Required 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment.

-Please keep the area around the breaker panels clear