Case: T10FR01233

Parcel: 13510150H

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
08/04/2010 INSP - FULL Approved approved
06/22/2010 INSP - FULL Correction Required 1. _____ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, back-up power shall be supplied
- Provide back up power supply for all required exit illumination ON FRONT EXIT

2. _____ 1024.6 Access to a public way. The exit discharge shall provide a direct and unobstructed access to a public way.
- REAR EXIT IS BLOCKED WITH A GATE

3. _______ 904.11.1 Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area a minimum of 10 feet (3048 mm) and a maximum of 20 feet (6096 mm) from the kitchen exhaust system. The manual actuation device shall be installed not more than 48 inches (1200 mm) nor less than 42 inches (1067 mm) above the floor and shall clearly identify the hazard protected. The manual actuation shall require a maximum force of 40 pounds (178 N) and a maximum movement of 14 inches (356 mm) to actuate the fire suppression system
-TRAIN EMPLOYESS ON THE ACTIVATION OF THE HOOD SYSTEM