Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/20/2010 | VIOL - MEANS OF EGRESS | Approved | All approved / closed | |
| 06/21/2010 | VIOL - MEANS OF EGRESS | Violation | Double keyed locks on doors: 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ______ Remove Keyed dead bolts. [front and side office door] They may be replaced with "Thumb turn" locks. [not the one with panic hardware. |
|
| 06/21/2010 | VIOL - MEANS OF EGRESS | Violation | Panic Hardware: TFC2006 / 1028.8 [Tucson Fire Code Modifications] Where panic hardware and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code. ______Remove lock constraint and keep it this way. [office] |
|
| 06/21/2010 | VIOL - MEANS OF EGRESS | Violation | Exit sign not lit: TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____Fix light in exit sign and back up battery power too. |
|
| 06/21/2010 | VIOL - MEANS OF EGRESS | Violation | Pool Gate: TFC 1008.2 Gates. Gates serving the means of egress system shall comply with the requirements of this section. Note: Pool gates are subject to the Pima County Spa /Pool Code. [Section AG105.2 Subsection 2 B - Gates shall be self closing and self latching.] ______ Fix and adjust gate to comply with this code. |