Case: T10FR01164

Parcel: 99999999A

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR01164

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
08/13/2010 VIOL - MEANS OF EGRESS Approved
06/14/2010 VIOL - MEANS OF EGRESS Violation Panic Hardware:

TFC2006 / 1028.8 [Tucson Fire Code Modifications] Where panic hardware and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code.

______Remove lock permanently on panic hardware door from pool table room.
06/14/2010 VIOL - MEANS OF EGRESS Violation Exit signs not lit:

TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated.

_____Fix light in exit signs.
06/14/2010 VIOL - MEANS OF EGRESS Violation Emergency lighting:

IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located]

______Fix all inoperative emergency lights.