Case: T10FR01164

Parcel: 99999999A

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T10FR01164

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
08/13/2010 VIOL - BUILDING SVCS & SYSTEMS Approved
06/14/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cords:

TFC2006/ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

_____ Remove or replace with approved fused power strip.
06/14/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Multiplug adapters:

TFC2006/ 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.

______Remove noncomplying devices.
06/14/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Open wire boxes/ splices:

TFC2006 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

______Cover wires in an approved manner.
06/14/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Electric Room signs:

605.3.1 Labeling. Doors into electrical control panel rooms
shall be marked with a plainly visible and legible sign stating
ELECTRICAL ROOM or similar approved wording.
The disconnecting means for each service, feeder or branch
circuit originating on a switchboard or panelboard shall be
legibly and durably marked to indicate its purpose unless
such purpose is clearly evident.

______ Mark each electric room, in each building, with a sign - Red Letters on White background- Stating "Fire Dept- Electric room" or something to this effect.
2" or 3" letters will be ok.