Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T10FR01163
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/28/2010 | INSP - FULL | Approved | ||
06/14/2010 | INSP - FULL | Correction Required | 1. _____ 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. - IN STORAGE ROOM - ALSO SHALL NOT EXTEND THROUGH WALLS 2. _____ 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. - PLACE BLANKS WHERE BREAKERS ARE MISSING IN STORAGE ROOM 3. _____ 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official. - DO NOT BLOCK EXIT PATHWAYS (STAIRS) 4. _____ 3405.3.6.2.7 Installation. Machines shall be installed in accordance with their listings. - REPAIR PARTS CEANER: LIGHT AND MISSING SOLDER LINK 5. _____ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. - TEST FIRE SPRINKLER SYSTEM - SERVICE FIRE EXTINGUISHERS - DO NOT LOAD FIRE SPRINKLER PIPING 6. _____ 2703.5.1 Markings. Individual containers, cartons or packages shall be conspicuously marked or labeled in an approved manner. Rooms or cabinets containing compressed gases shall be conspicuously labeled: -LABEL ANTIFREEZE CONTAINERS IN THE BASEMENT 8. _____ 105.6.16 #3 Flammable and combustible liquids. An operational permit is required to… store, handle or use Class II or Class IIIA or class IIIB liquids in excess of 25 gallons (95 L) in a building or in excess of 60 gallons (227 L) outside a building, except for fuel oil used in connection with oil-burning equipment. -OBTAIN PERMITS FOR YOUR TANKS (HANDOUT PROVIDED) 9. _____ 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used: - REPLACE MISSING COVERPLATE NEAR UST'S |