Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T10FR01150
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/24/2010 | INSP - FULL | Approved | An order was given to add nozles and upgrade the kitchen extinguishing system. Refer to T10FR01247. ____________________________ { John Bieg } ____________________________ { Captain Leach } |
|
| 06/11/2010 | INSP - FULL | Correction Required | NOT ENOUGH PROTECTION BY SYTEM TO COVER SALAMANDER, RANGE & GRIDDLE. NEED A BIGGER TANK (3GAL) TO COVER ALL APPLIANCES |