Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T10FR01122
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/08/2010 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm). 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. ______ properly hang all portable fire extinguishers according to code |