Case: T10FR01090

Parcel: 116170060

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
09/09/2010 INSP - FULL Approved The deficiency noted about the separation distance for the fryer and the range has been corrected by using a stainless steel partition. The extinguishing system is an old dry chem system that passed inspection by United Fire within the last 6 months. THe system is compliant.


____________________________
( Inspector John Bieg )


___________________________
( Captain )
06/03/2010 INSP - FULL Correction Required Non compliance tag on system - fryers shall be installed with at least a 16 inch space between the appliance and flames of another
Wet chemical systems shall comply with the UL 300 Testing standard