Case: T10FR01089

Parcel: 13419042A


Addresses:

7114 E BROADWAY BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T10FR01089

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
06/17/2010 INSP - FULL Approved all items abated
06/03/2010 INSP - FULL Correction Required 1.
_____ 3003.5 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel in accordance with Sections 3003.3.1 through 3003.3.3.

2. _____ 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exits:
- In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in churches, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided:
2.1. The locking device is readily distinguishable as locked,
2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25mm)high on a contrasting background,
2.3. The use of the key-operated locking device is revokable by the fire code official for due cause.

3. _____ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, back-up power shall be supplied
- Provide back up power supply for all required exit illumination