Case: T10FR01074

Parcel: 113030820


Addresses:

3620 N 1ST AV

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
06/02/2010 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.6 Unapproved conditions
Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided for all switch and outlet covers.

_____ Place approved cover over the missing electrical panel

605.4 Multi-plug adapters
Multi-plug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC electrical code shall be prohibited.

_____ All Multi-plug adapters shall be removed or replace with approved fused power strips.