Case: T10FR01046

Parcel: 13510150R

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T10FR01046

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
06/16/2010 INSP - FULL Approved all abated
05/27/2010 INSP - FULL Correction Required 1. _____ 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed:
- All fire extinguishers shall be service
- One fire extinguisher is missing near receiving

2. _____ 3003.5 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel in accordance with Sections 3003.3.1 through 3003.3.3.
- Near main freezer

3. _____ 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.
- Maintain proper clearance
- Provide a sign on the door that states, "Electrical Room"

Note: Obtain keys for fire exit doors alarm. the remainign exit will be checked upon re-inspection.