Case: T10FR01043

Parcel: 10321342A


Addresses:

2126 W GRANT RD


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T10FR01043

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
05/27/2010 VIOL - BUILDING SVCS & SYSTEMS Correction Required IFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

_____1. Remove the extension cord used to power the OPEN sign.
NOTE: Replace it with a fused multi-plug adapter.
05/27/2010 VIOL - BUILDING SVCS & SYSTEMS Correction Required IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

_____1. Repair the brocken electrical outlet located on the north wall by the nail stations.


________________________________________________
(John E. Bieg, Fire Inspector, Tucson Fire Department)

I, ______________________ have received a copy of this inspection report. (Building Representative)


______________________________
(Captain)


Re-inspection scheduled on or after _____/_____/_____
Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions.


All noted Tucson Fire Code violations have been corrected: _____/_____/_____

______________________
John E. Bieg