Case: T10FR01030

Parcel: 13510150R


Addresses:

2419 S KOLB RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T10FR01030

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
06/28/2010 INSP - FULL Approved
05/25/2010 INSP - FULL Correction Required _____ 3403.5.3 Warning labels. Individual containers, packages and cartons shall be identified, marked, labeled and placarded in accordance with federal regulations and applicable state laws.
- lABEL BATTERY AREA "CORROSIVES"
05/25/2010 INSP - FULL Correction Required _____ 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
- TWO EACH AT FRONT DEST
05/25/2010 INSP - FULL Correction Required _____ 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.
05/25/2010 INSP - FULL Correction Required _____ 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
- REAR EXIT (EAST)
05/25/2010 INSP - FULL Correction Required _____ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, back-up power shall be supplied
- REAR EXIT (EAST)
- ABOVE FRON TCOUNTER
- ABOVE THE EXAUST AISLE
05/25/2010 INSP - FULL Correction Required _____ 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used:
- BEHIND THE "COMMERCIAL" DEST
05/25/2010 INSP - FULL Correction Required _____ 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official.
- REAR EXIT (SOUTH)
NOTE: CORRECTED IN MY PRESENCE