Case: T10FR01022

Parcel: 13216600B


Addresses:

4220 S PARK AV


Inspection Status: Approved

Inspection History: INSP - UST

Case Number - T10FR01022

Inspection Description - INSP - UST

Inspection Status - Approved

Date Description Inspector Results Comments
06/16/2010 INSP - UST Approved Tightness test recieved. Approved
06/07/2010 INSP - UST Partial Approval Line pressure and soap test passed. Line leak and sump test will be done next week.
05/21/2010 INSP - UST Continued Received notification of leak (less than 8 Gallons) into sump secondary containment. No release to the environment. Transition fitting will be replaced. Leak is contained and cleaned. UST is out of service at this time and will remain so until inspected by the Tucson Fire Department.