Inspection Status: Approved
Inspection History: INSP - UST
Case Number - T10FR01022
Inspection Description - INSP - UST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/16/2010 | INSP - UST | Approved | Tightness test recieved. Approved | |
06/07/2010 | INSP - UST | Partial Approval | Line pressure and soap test passed. Line leak and sump test will be done next week. | |
05/21/2010 | INSP - UST | Continued | Received notification of leak (less than 8 Gallons) into sump secondary containment. No release to the environment. Transition fitting will be replaced. Leak is contained and cleaned. UST is out of service at this time and will remain so until inspected by the Tucson Fire Department. |