Case: T10FR01014

Parcel: 133091100


Addresses:

8225 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T10FR01014

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
07/16/2010 VIOL - BUILDING SVCS & SYSTEMS Approved
05/21/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cords:

TFC2006/ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

_____ Remove or replace with approved fused power strip.
05/21/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Open space in electrical panel:

TFC2006 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.

_____Place an approved "blank" in the space. [boiler room]
05/21/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Multiplug adapters:

TFC2006/ 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.

______Remove noncomplying devices. [office, shop, laundry- behind dryers]