Case: T10FR01000

Parcel: 133340120


Addresses:

9000 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR01000

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
08/13/2010 VIOL - MEANS OF EGRESS Approved All approved /closed
05/18/2010 VIOL - MEANS OF EGRESS Violation Double keyed lock on door:
1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

______ Remove Keyed dead bolt. [weight room, office, laundry room x2]
05/18/2010 VIOL - MEANS OF EGRESS Violation Exit signs not lit:

TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated.

_____Fix lights in exit signs.
05/18/2010 VIOL - MEANS OF EGRESS Violation Emergency lighting:

IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located]

______Fix all inoperative emergency lights.
05/18/2010 VIOL - MEANS OF EGRESS Violation Pool Gate:
TFC 1008.2 Gates. Gates serving the means of egress system shall
comply with the requirements of this section. Note: Pool gates are subject to the Pima County Spa /Pool Code.
[Section AG105.2 Subsection 2 B - Gates shall be self closing and self latching.]

______ Pool gate must comply with Pima County Pool Code.