Case: T10FR00937

Parcel: 134234110


Addresses:

6366 E BROADWAY BL


Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T10FR00937

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
05/10/2010 INSP - FULL Violation TFC 107.1 - Maintenance of safeguards.
Whenever or wherever any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provisions of this code, or otherwise installed, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with this code and applicable referenced standards.

Correct deficiencies as noted in United Fire hood system deficiency report 382146….
_____ Appliance location
_____ Branch exhaust ducts shall be protected by system
_____ Hood system penetrations
* Pull station need not be relocated

Exit Sign Illumination
_____Kitchen door

_____ Repair all emergency lights


TFC 901.6 - Inspection, testing and maintenance.
Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

_____ All sprinkler heads and escutcheons shall be cleaned, replaced, or adjusted to meet the requirements of this code. (Side Kitchen)

_____ Extinguishers shall be inspected by occupant monthly and professionally serviced annually. A tag shall be affixed to the extinguisher with records of these activities.


3003.5.3 - Securing compressed gas containers, cylinders and tanks.
Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods:
1) Securing containers, cylinders and tanks to a fixed object with one or more restraints.

_____ chain/secure CO2 canisters behind bar

TFC 703.1 - Maintenance
The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire.

Replace missing ceiling tiles.
_____ liquor closet
_____ waitress area


TFC 605.5 - Extension cords
Extension cords and flexible cords shall not be a substitute for permanent wiring….

_____ Air conditioner - liquor closet